Getriebebau NORD GmbH & Co. KG
Rudolf-Diesel-Straße 1 · D-22941 Bargteheide
Tel.: +49 45 32 - 40 10 · Fax: +49 45 32 - 40 12 53 · www.nord.com
Overvoltage filter
1.0 First edition 03.11.10 Rck
TI 030 276997071 2/2
1.1 Supplement to UL/cUL approval conditions, tightening torques in lb-in 24.02.12 Rck
Version Change Date Name Document Page
1U2 (L11)
1V2 (L21)
1W2 (L31)
PE (PE1)
Line choke SK CI1-460/x-C
1U1 (L1)
1V1 (L2)
1W1 (L3)
Netzdrossel SK CI1-460/x-C
PE (PE2)
L3 (L32)
L2 (L22)
L1 (L12)
Frequenzumrichter
Netzanschluss -
Inverter
Mains supply -
Befestigungselement
4x für M4
Fastening element
Netz Filter-CSA SK CIF-323-40 / SK CIF-340-60 - Montagehinweise
Line Filter-CSA SK CIF-323-40 / SK CIF-340-60 - Installation hints
Optional:
Modifications for on-wall mounting
- Remove fixing screws
- Remove side frames
- Screw on alternate side frames
- Plug fastening elements in
Optional:
Umbau aus Wandmontage
- Befestigungsschrauben lösen
- Seitenteile abnehmen
- Seitenteile für Wandmontage aufsetzen
- Befestigungselemente anstecken
NS 35/7,5
- optional for SK CIF-340-60
- optional für SK CIF-340-60
SK CIF-340-60
SK CIF-323-40
SK CIF-340-60
SK CIF-323-40
Connections:
Input and output Screw/plug-in terminal 0.5 … 25 mm²
L1/L2/L3/PE
Terminal screw tightening torque 2.5 Nm (22 lb-in)
Schematic circuit diagram of electrical connection:
Installation data:
Dimensions: [mm] L 180.5 x W 126 x D 71 (Snap-on rail mounting)
L 204,5 x B 126 x T 57
(on-wall mounting)
Scope of delivery:
Voltage limitation filter without additional accessories with 4 off removable fastening elements for on-wall mounting.
UL/cUL approval(supplement to specifications in the frequency inverter manual):
"Use 75°C Copper Conductors Only"
"Connection of copper cable with an insulation rating of at least 75°C"
(only refers to connection cables (mains and motor cables but not control cables)
These products are intended for use in a pollution degree 2 environment“
"The product is suitable for operation in a pollution degree 2 environment"
“Total SCCR of the combination (drive and transient surge suppression device) will be determined by the max. SCCR rating
of the drive according the drive manual or label, type and rating of the Branch Circuit Protection.”, or equivalent. Protection as
described in drive manual, for example type J, T fuses or inverse time trip type circuit breaker.
The total short-circuit current rating of the combination (SK CIF and frequency inverter) is determined by the maximum short-
circuit current rating of the connected frequency inverter. Protection as described in the frequency inverter manual by
approved lead cut-outs or circuit breakers.